Do You Need Bigger Radiators for a Heat Pump?
Sometimes — but often fewer than people expect. A heat pump heats your radiators with cooler water than a boiler does, so each radiator gives out less heat. Whether yours are big enough depends on how much heat each room actually needs. This guide explains the sums, shows how to check a room yourself, and sets out the options when a radiator falls short.
Why a heat pump changes the answer
A gas or oil boiler traditionally sends water to the radiators at 70–80 °C (160–180 °F). A heat pump can do that too, but its efficiency drops sharply the hotter it has to make the water. Heat pump systems are therefore designed to run at about 45–55 °C (113–131 °F) on the coldest days, and cooler the rest of the time.
A radiator’s output depends on how much hotter it is than the room. Cooler water means less heat from the same radiator, so to keep the room just as warm, the radiator has to be bigger — or the room has to need less heat.
How much output a radiator loses
Radiator outputs in catalogues are quoted at ΔT50: the water in the radiator averages 50 °C warmer than a 20 °C room. At a lower ΔT, the output falls according to a standard formula from the radiator testing standard, EN 442:
Actual output = catalogue output × (ΔT ÷ 50)^1.3
| ΔT | Approx. flow temperature | Typical system | Output vs. catalogue | Radiator rating needed |
|---|---|---|---|---|
| ΔT50 | 75 °C (167 °F) | Traditional boiler — the catalogue rating | 100% | 1.0 × heat loss |
| ΔT40 | 65 °C (149 °F) | Condensing boiler turned down | 75% | 1.3 × heat loss |
| ΔT30 | 55 °C (131 °F) | Heat pump, higher setting | 51% | 1.9 × heat loss |
| ΔT25 | 50 °C (122 °F) | Heat pump, typical design | 41% | 2.5 × heat loss |
| ΔT20 | 45 °C (113 °F) | Heat pump, efficient design | 30% | 3.3 × heat loss |
So at a typical heat pump design of ΔT25, a radiator gives about 41% of the figure in the catalogue, and you need a rating of roughly 2.5 times the room’s heat loss. Flow temperatures are approximate: they assume a 20 °C room and water that cools by about 5–10 °C as it passes through the radiator.
Check a room in three steps
- Find the room’s heat loss. Use the BTU calculator: enter the room size, outside walls, windows and insulation level. It gives the heat the room needs on a cold day, in watts and BTU per hour.
- Find your radiator’s rated output. Measure its height and length and note its type — single panel, double panel, and how many rows of convector fins. Look up that size in any manufacturer’s catalogue to get its ΔT50 output. If the room has two radiators, add them together.
- Compare. Choose “Heat pump” as the heating system in the calculator and it shows the ΔT50 rating to look for. If your radiators add up to that or more, they are big enough.
Worked example
A 4.5 × 3.5 m living room with two outside walls in an averagely insulated house needs about 1,000 W (3,400 BTU/h) when it is −3 °C outside. It has one double-panel, double-convector radiator, 600 mm high and 1,000 mm long, rated at about 1,700 W at ΔT50.
- With a boiler at ΔT50: 1,700 W against a 1,000 W need — plenty to spare.
- With a heat pump at ΔT25: 1,700 × 0.41 ≈ 700 W — about 300 W short on the coldest days.
- What would work: a ΔT50 rating of about 2,450 W. A radiator of the same type about 1,400–1,500 mm long would do it, and a triple-panel radiator the same size as the old one would come close.
Notice that the existing radiator was already 70% bigger than the boiler needed. Many radiators are oversized like this, which is why plenty of rooms need no change at all.
What to do if a radiator is too small
- Reduce the heat loss first. Loft insulation, draught-proofing and better glazing cut the heat the room needs — and so the radiator size — while lowering bills whatever the heating system. See the insulation calculator and how to insulate a loft or attic.
- Fit a deeper radiator the same size. Swapping a single panel for a double, or a double for a triple, can raise output by roughly 40–80% without taking up more wall, and often reuses the same pipe positions.
- Fit a longer or taller radiator, or add a second one, where there is wall space.
- Consider fan-assisted radiators or underfloor heating in rooms where wall space is short. Both work well at low water temperatures.
- Accept a slightly higher flow temperature. Running at ΔT30 instead of ΔT25 means radiators about 20% smaller, at some cost in efficiency. It can be a sensible compromise if only one or two rooms fall short.
Things that are often overlooked
- Pipework. Heat pumps move more water at a smaller temperature drop than boilers, so very narrow pipes (such as 8–10 mm microbore) can limit how much heat reaches a radiator. An installer will check this.
- Bedrooms need less. They are usually kept at about 18 °C, which both lowers the heat loss and raises the radiator’s ΔT.
- Weather compensation. A well set-up heat pump lowers the water temperature in milder weather, so radiators feel warm rather than hot for long periods. That is normal, and it is where the efficiency comes from.
- North America. The same sums apply to hot-water baseboard and cast-iron radiators fed by an air-to-water heat pump: baseboard is usually rated for 180 °F water and gives far less at 120–130 °F. Homes with ducted air systems do not have this issue — there the ducts and airflow are what need checking.
What this means for running costs
The lower the water temperature a heat pump can run at, the less electricity it uses for the same heat — which is the reason to size radiators generously rather than just adequately. To see how a heat pump’s running cost compares with gas, oil or direct electric heating at different efficiencies, use the heating cost calculator.
The checks here are a first estimate for one room. Before buying a heat pump or new radiators, get a room-by-room heat loss survey from a qualified installer — in the UK, one certified under MCS; in the US, a contractor who carries out a Manual J load calculation.